# EL 2.1 FW 1.3.0 Modbus TCP Communication Interface

# Introduction

Refer to the Reference section for details of the Modbus protocol.

This document describes public Modbus TCP implementation for Enapter Electrolyser EL 2.1 and assume understanding of TCP/IP and Modbus protocols.

# Physical Interface Connection

Connect Ethernet cable to the Ethernet Port of Enapter EL 2.1 electrolyser.

# TCP/IP Connection Settings

By default DHCP client is enabled therefore IP address will be assigned automatically by DHCP server available in the connected network.

It is recommended to set DHCP reservation based on MAC address of the electrolyser.

Configuration of the Static IP is possible using Enapter Cloud and Enapter Mobile Application for iOS and Android.

# Modbus Connection Settings

Option Value Comment
Modbus Port 502
Modbus Slave Address 1 Enapter Electrolyser always addressed as a slave

# References

http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf (opens new window)

# Data Formats Used

Primary tables Object Type Permission Comment
Input Registers 16 bit word Read Only
Holding Registers 16 bit word Read / Write

# Data Bits/Registers Dimension

Data Type Size in Bits Registers Used Comment
Boolean 16 bits 1 register 0 value means 'false', all other cases - 'true'
Uint16 16 bits 1 register
Uint32 32 bits 2 registers
Uint64 64 bits 4 registers
Float32 32 bits:
* bit 31: Sign (1 bit)
* bit 30-23: Exponent (8 bits)
* bit 22-0: Fraction (23 bits)
2 registers IEEE 754 Single-precision floating-point

# Data Encoding

Big-endian, high word first data encoding used.

This means that when more than single byte (8 bits) is transmitted, network byte order is used - the most significant byte placed at lower address (sent first).

# Implemented Modbus Functions

Function Code Comment
Read Holding Registers 03
Read Input Registers 04
Write Single Holding Register 06
Write Multiple Holding Registers 16

# Modbus Data Model

Input registers and Holding registers are referred to in the range 3XXXX and 4XXXX respectful (also known as PLC Address). For example, Holding register 0 in this document would be referred to as 40001 and would be addressed as register 0000 in the data address field of the Modbus message (also known as Protocol Address).

# Events

# Severity Levels

Code Severity Level LED Indication Description Comment
F Fatal Error Red and Yellow Blinks System stopped. Unrecoverable error. Hardware repair required. e.g. Pressure sensor is not connected or broken.
E Error Red Blinks System Stopped. Recoverable error. e.g. No input water pressure and internal water tank is empty.
W Warning Yellow Blinks Heads-up event which should be taken into account to avoid Error or Fatal Error. e.g. No input water pressure and internal water tank is full.

# Routines

Code Routine Comment
P Platform
C Electrolyte Circulation
D Stack Ramp Down
R Water Refilling
S Steady Hydrogen Production
T Temperature Management
U Stack Ramp Up
X Safety Check
F Anti-freezing
L Leakage Test
O Blowdown
H Heartbeat

# Warning, Error and Fatal Error Codes

Code Name Severity Code Routine Code Component Condition Description
0x0000 none -- -- -- No error
0x0FFF int -- -- -- Unexpected error, hardware failure, read logs for details
0x1F81 FP_01 F P -- Voltage < 2.9V Brownout detected, restore power and reset system
0x1F82 FP_02 F P -- Updated firmware have new mandatory settings New parameters has been added to configuration, please re-check and write new one, contact enapter support or certified partner
0x3F84 WP_04 W P -- Button
0x108A FC_10 F C P107 Pump broken
0x1114 FD_20 F D PT101A Pressure drop > 2% Hydrogen leaks
0x318A WR_10 W R PT105 Pressure > 5barg Water inlet pressure too high
0x3194 WR_20 W R PT105 Pressure < 0.5barg Water inlet pressure too low
0x118A FR_10 F R LSHH102A Water level over level switch Electrolyte level too much high
0x1194 FR_20 F R LSL102D Water level below level switch Electrolyte level too much low
0x11B2 FR_50 F R LSL102D
LSM102C
Conflict between water sensors (low and medium level)
0x11B3 FR_51 F R LSM102C
LSH102B
Conflict between water sensors (medium and high level)
0x11B4 FR_52 F R LSH102B
LSHH102A
Conflict between water sensors (high and very high level)
0x11A8 FR_40 F R -- Check water leaks
0x3195 WR_21 W R -- Refilling timeout (won't be shown if WR_10 or WR_20 is present)
0x31B3 WR_51 W R LSL102D Drain completely (available only in Maintenance Mode)
0x31B4 WR_52 W R LSL102D Refill to high level (available only in Maintenance Mode)
0x3215 WS_21 W S PT101A Pressure spike > 2% Drifting PT101A
0x3216 WS_22 W S LSM102C System works with electrolyte level less than medium one and can not refill (during pressure limit and etc) Too low water level
0x128A FT_10 F T TT106 Temperature > 58°C Electrolyte temperature too high
0x3294 WT_20 W T F103A Rotation < 600rpm Electrolyte cooling fan broken
0x228A ET_10 E T TT102A Temperature < 6°C Electrolyte temperature too low
0x330A WU_10 W U PT101A Pressure is > atmospheric pressure + 10% Gas side pressure is not atmospheric. Ramp-Up is not possible (pressure too high for start)
0x1401 FX_01 F X PT101A Pressure > 37bar Hydrogen inner pressure too high
0x1402 FX_02 F X WPS104 Water sensor is wet Water presence
0x1403 FX_03 F X PSU 48V No voltage from PSU PSU broken
0x1404 FX_04 F X HASS Current > 58A Stack current too high
0x1405 FX_05 F X TSH106 Backflow temperature too high
0x1406 FX_06 F X PT101A Hydrogen leaks
0x1407 FX_07 F X TS108 Temperature > 75°C Electronic board temperature too high
0x1408 FX_08 F X PSH102 Electrolyte tank pressure too high
0x1409 FX_09 F X TSLL102B Electrolyte temperature too low
0x140A FX_10 F X PSHH101B Hydrogen pressure too high
0x141E FX_30 F X PT105 Water inlet pressure transmitter broken
0x141F FX_31 F X TT102A Electrolyte tank temperature transmitter broken
0x1420 FX_32 F X FM106 Electrolyte flow meter broken
0x1421 FX_33 F X TT106 Electrolyte backflow temperature transmitter broken
0x1422 FX_34 F X PT101A Hydrogen inner pressure transmitter broken
0x1423 FX_35 F X PT101C Outer hydrogen pressure transmitter broken
0x1424 FX_36 F X F1084B Rotation < 3000rpm Chassis circulation fan broken
0x1425 FX_37 F X F108C Rotation < 3000rpm Electronic compartment cooling fan broken
0x1426 FX_38 F X TS108 Electronic board temperature transmitter broken
0x1427 FX_39 F X HASS Current sensor broken
0x1428 FX_40 F X External switch Dry contact error
0x148A FF_10 F F -- Frozen pipes
0x1501 FL_01 F L -- Huge H2 leak detected
0x358A WO_10 W O PT101C Pressure > 25 barg Outer pressure is too high to run blowdown routine
0x3594 WO_20 W O -- The Blowdown procedure will be started at H2-production start
0x159E FO_30 F O PT101C The purge line is obstructed or the adjustable check valve (CV101B) cracking pressure is set incorrectly
0x360A WH_10 W H ModBus Heartbeat Packet was not received in time Lost ModBus safety heartbeat communication
0x360B WH_11 W H Gateway Heartbeat Packet was not received in time Lost Gateway safety heartbeat communication
0x360C WH_12 W H UCM Heartbeat Packet was not received in time Lost UCM safety heartbeat communication

# Modbus Table

# Holding Registers (Read / Write)

Register Data Type Name Comment
0 Uint64 Unix Time Seconds from 1 January 1970 UTC.
e.g. 02/29/2020 @ 3:15 PM (UTC) represented as 1582989315.
4 Boolean Reboot 1 = Reboot.
5 Boolean Locate Electrolyser 1 = Start Blinking All LED; 0 = Stop Blinking All LED.
6 Boolean Maintenance Mode 1 = Enable Maintenance Mode; 0 = Disable Maintenance Mode.
9 Boolean Factory Reset True = enable (possible only in Expert Mode)
1000 Boolean Start / Stop Electrolyser 1 = Start; 0 = Stop.
1002 Float32 Production Rate [%] Current production rate in percent (system reset set this value to 'Default Production Rate'), can be changed 'on-fly' even when electrolyser produce H2
1010 Boolean Request Blowdown routine 1 = Request blowdown or read 'is blowdown requested'
4000 Boolean Configuration Begin 1 = Start configuration
4001 Boolean Configuration Commit 1 = Commit current changes; 0 = Rollback changes
4020 Uint32 Ethernet IP Address e.g. 0xC0A80201 (192.168.2.1); 0 = DHCP enabled
4022 Uint32 Ethernet IP Netmask
4024 Uint32 Ethernet Gateway IP Address
4308 Float32 Max Tank Pressure (Outlet) bar
4310 Float32 Restart Pressure (Outlet) bar
4396 Float32 Default Production Rate [%] This register can be modified only when stack is inactive (Idle or Maintenance mode)
4474 Float32 Electronic fan maximal rotation speed in percent, default = 100
4476 Float32 Electronic fan minimal rotation speed in percent, default = 10
4600 Uint32 Heartbeat ModBus Timeout Seconds; 0 = disable
4602 Uint32 Heartbeat Gateway Timeout Seconds; 0 = disable
4604 Uint32 Heartbeat UCM Timeout Seconds; 0 = disable

# Input Registers (Read Only)

Register Data Type Name Comment
0 Uint32 Device Model 0x454C3231 for EL 2.1
2 Uint16 Firmware MAJOR and MINOR Version Ex: 267 => 267 // 256 = 1, 267 % 256 => 11 (1.11)
3 Uint16 Firmware PATCH Version Ex: 3 => 3 (3)
4 Uint32 Firmware Build Number e.g. 0x4E343471
6 Uint128 Device Control Board Serial Number 9E25E695-A66A-61DD-6570-50DB4E73652D
14 Uint64 Cabinet (Chassis) Serial Number 19030125124810
18 Uint16 System State 0 = Internal Error, System not Initialized yet; 1 = System in Operation; 2 = System Halted (e.g. during error); 3 = System in Maintenance Mode; 4 = Fatal Error; 5 = System in Expert Mode.
20 Uint32 Live time [seconds] Total time during which a system is power up (not only time when stack is working).
22 Uint32 Uptime [seconds] How long the system has been running
768 Array of 32 Warning Events Warning Events Array Warning Events Array represented by Error Codes. First Uint16 contains total quantity of Warning Events.
832 Array of 32 Error Events Error Events Array Error Events Array represented by Error Codes. First Uint16 contains total quantity of Error Events.
1000 Uint32 Product Code 0x00 = ELE210535A2AXV01_03
0x01 = ELE210508A2AXV01_03
0x02 = ELE210535A2AXV04
0x03 = ELE210508A2AXV04
0x04 = ELE210535A2LSV01
1002 Uint32 Stack Start/Stop Cycles Quantity
1004 Uint32 Stack Total Runtime seconds
1006 Float32 Stack Total H2 Production NL
1008 Float32 H2 Flow Rate NL/hour, NAN when not producing H2;
1200 Uint16 Electrolyser State 0 = Halted; 1= Maintenance mode; 2 = Idle; 3 = Steady; 4 = Stand-By (Max Pressure); 5 = Curve; 6 = Blowdown.
4000 Boolean Configuration Progress 1 = Configuration is in progress.
4001 Boolean Configuration Source 1 = Configuration over Modbus.
4002 Int32 Last Configuration Result 0 = OK, Configuration was completed successfully; 1 = Permanent, The operation has failed (internal or general error); 2 = No Entry, Configuration was not started or interrupted; 5 = I/O, Data save error; 11 - Try again, Configuration needs to be tried again; 13 = Access Denied, Some changed registers are read-only; 16 = Busy, Another configuration was in progress; 22 = Invalid, The data has invalid or wrong type.
4004 Uint16 Last Configuration Wrong Holding Keeps first invalid Holding register number which doesn't allow successful configuration commit.
4600 Uint16 Heartbeat
6000 Uint16 Dryer Error Dryer error code (bitmask). Reserved, not implemented yet.
6001 Uint16 Dryer Warning Dryer warning code (bitmask). Reserved, not implemented yet.
6002 Float32 Dryer TT00 Temperature of heater element for cartridge 0 (first line). Reserved, not implemented yet.
6004 Float32 Dryer TT01 Temperature of heater element for cartridge 1 (first line). Reserved, not implemented yet.
6006 Float32 Dryer TT02 Temperature of heater element for cartridge 2 (first line). Reserved, not implemented yet.
6008 Float32 Dryer TT03 Temperature of heater element for cartridge 3 (first line). Reserved, not implemented yet.
6010 Float32 Dryer PT00 Input pressure of the dryer. Reserved, not implemented yet.
6012 Float32 Dryer PT01 Output pressure of the dryer. Reserved, not implemented yet.
7000 Boolean High Electrolyte Level Switch (LSH102B_in) 1 = Electrolyte level over sensor; 0 = Electrolyte level below sensor.
7001 Boolean Very High Electrolyte Level Switch (LSHH102A_in) 1 = Electrolyte level over sensor; 0 = Electrolyte level below sensor.
7002 Boolean Low Electrolyte Level Switch (LSL102D_in) 1 = Electrolyte level over sensor; 0 = Electrolyte level below sensor.
7003 Boolean Medium Electrolyte Level Switch (LSM102C_in) 1 = Electrolyte level over sensor; 0 = Electrolyte level below sensor.
7004 Boolean Electrolyte Tank High Pressure Switch (PSH102_in) 1 = Pressure is too high; 0 = Pressure is normal.
7005 Boolean Very High Hydrogen Pressure Switch (PSHH101B_in) 1 = Pressure is too high; 0 = Pressure is normal.
7006 Boolean Downstream High Temperature Switch (TSH106_in) 1 = Temperature is too high. 0 = Temperature is normal.
7007 Boolean Electronic Compartment High Temperature Switch (TSH108_in) 1 = Temperature is too high. 0 = Temperature is normal.
7008 Boolean Very Low Electrolyte Temperature Switch (TSLL102B_in) 1 = Temperature is too low. 0 = Temperature is normal.
7009 Boolean Chassis Water Presence Switch (WPS104_in) 1 = Water is present on input; 0 = No water input.
7500 Float32 Electrolyte Cooler Fan Speed (F103A_in_rpm) [rpm]
7502 Float32 Air Circulation Fan Speed (F104B_in_rpm) [rpm]
7504 Float32 Electronic Compartment Cooling Fan Speed (F108C_in_rpm) [rpm]
7506 Float32 Electrolyte Flow Meter (FM106_in_lmin) [Liters per minute]
7508 Float32 Stack Current (HASS_in_a) [Ampere]
7510 Float32 PSU Voltage Signal (PSU_in_v) [Volt]
7512 Float32 Inner Hydrogen Pressure (PT101A_in_bar) [bar]
7514 Float32 Outer Hydrogen Pressure (PT101C_in_bar) [bar]
7516 Float32 Water Inlet Pressure (PT105_in_bar) [bar]
7518 Float32 Electrolyte Temperature (TT102A_in_c) [°C]
7520 Float32 Downstream Temperature (TT106_in_c) [°C]
8000 Float32 Inner Hydrogen Pressure Raw Sensor Value (PT101A_in_v) Raw value, [Volt]
8002 Float32 Outer Hydrogen Pressure Raw Sensor Value (PT101C_in_v) Raw value, [Volt]
8004 Float32 Stack Current Raw Sensor Value (HASS_in_v) Raw value, [Volt]

# Diagrams

# System State Diagram

This diagram describes possible transition between different electrolyser states. The state can be read in the Input Register #18.

# Examples

# Example: Change Electrolyser Restart Pressure Flow

Here is an example to change Electrolyser Restart Pressure to 25 bar. This will enable Electrolyser to restart when pressure drop to 25 bar on outlet.

# Example: Reading Modbus Input Registers

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Word Count
    00 01 00 00 00 06 01 04 03 EE 00 02
  • Request Packet Description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Read Input Registers – default: 04
    • Reference Number: Starting register – decimal: 1006
    • Word Count: Number of registers to read – decimal: 2
  • Wireshark Example

    Reading Modbus Request

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Byte Count Register[0] Register[1]
    00 01 00 00 00 07 01 04 04 48 00 10 7A
  • Response Packet Description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol ID – default: 00 00
    • Query Length – decimal: 7
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Read Input Registers – default: 04
    • Byte Count: Registers values size – decimal: 4
    • Register[0] value – decimal: 18432
    • Register[1] value – decimal: 4218
    • Register[…] value – 2 bytes
  • Wireshark Example

    Reading Modbus Response

# Example: Writing to Modbus Holding Registers

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 01 00 00 00 06 01 06 00 04 00 01
  • Request Packet Description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Starting register – decimal: 4
    • Data: Value to write – decimal: 1
  • Wireshark Example

    Writing Modbus Request

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 01 00 00 00 06 01 06 00 04 01
  • Response Packet Description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Register to write – decimal: 4
    • Data: Value to write – decimal: 1
  • Wireshark Example

    Writing Modbus Response

# Example: Reading Errors Sequence

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Word Count
    00 01 00 00 00 06 01 04 03 40 00 20
  • Request packet description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol Identifier – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Read Input Registers – default: 04
    • Reference Number: Starting register – default: 03 40
    • Word Count: Number of registers to read – default: 00 20
  • Wireshark Example

    Reading Errors Request

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Byte Count Register[0] Register[1]
    00 01 00 00 00 43 01 04 40 00 01 11 B3
  • Response packet description

    Modbus/TCP

    • Transaction ID – default: 00 01
    • Protocol ID – default: 00 00
    • Query Length – default: 00 43
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Read Input Registers – default: 04
    • Byte count: Registers values size – default: 40
    • Register[0] value – total number of errors, decimal: 1
    • Register[1] value – error code 1: 11 B3
    • Register[…] value – error code N
  • Wireshark Example

    Reading Errors Response

# Example: Writing Heartbeat Modbus Timeout

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 02 00 00 00 06 01 06 0F A0 00 01
  • Request Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 2
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Starting register – decimal: 4000
    • Data: Value to write – decimal: 1
  • Wireshark Example

    Writing Heartbeat Modbus Timeout Request 1

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 02 00 00 00 06 01 06 0F A0 00 01
  • Response Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 2
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Register to write – decimal: 4000
    • Data: Value to write – decimal: 1
  • Wireshark Example

    Writing Heartbeat Modbus Timeout Response 1

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 03 00 00 00 06 01 06 11 F8 00 00
  • Request Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 3
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Starting register – decimal: 4600
    • Data: Value to write – decimal: 0
  • Wireshark Example

    Writing Heartbeat Modbus Timeout Request 2

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 03 00 00 00 06 01 06 11 F8 00 00
  • Response Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 3
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Register to write – decimal: 4600
    • Data: Value to write – decimal: 0
  • Wireshark Example

    Writing Heartbeat Modbus Timeout Response 2

  • Request Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 04 00 00 00 06 01 06 0F A1 00 01
  • Request Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 4
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Starting register – decimal: 4001
    • Data: Value to write – decimal: 1
  • Wireshark Example

    Writing Heartbeat Modbus Timeout Request 3

  • Response Packet

    Transaction ID Protocol ID Query Length Unit ID Function Code Reference Number Data
    00 04 00 00 00 06 01 06 0F A1 00 01
  • Response Packet Description

    Modbus/TCP

    • Transaction ID – decimal: 4
    • Protocol ID – default: 00 00
    • Query Length – default: 00 06
    • Unit ID: Slave Address – default: 01

    Modbus

    • Function Code: Write Single Register – default: 06
    • Reference Number: Register to write – decimal: 4001
    • Data: Value to write – decimal: 1